500 kV 交流同塔四回输电线路反击耐雷性能

柴雅静1 , 周文俊1 , 李雪1 , 刘小冬2 , 苏红梅2   

  1. 1.武汉大学电气工程学院, 湖北武汉430072; 2.河北电力科学研究院, 河北石家庄050000
  • 收稿日期:2007-02-05 出版日期:2007-09-20 发布日期:2017-07-05
  • 作者简介:柴雅静(1975 -), 女, 湖北武汉市, 在读博士
  • 基金资助:
    国家自然科学基金资助(No .59707004)。

Back Flashovers Lightning Perfo rmances fo r 500 kV AC T ransmission Lines Wi th Quadruple -Circui ts o n Single Tow er

  1. 1. School of Electrical Engineering, Wuhan University, Wuhan Hubei 430072, P.R. China;
    2. Hebei Electrical Power Research Institute, Shijiazhuang Hebei 050000, P.R. China
  • Received:2007-02-05 Published:2007-09-20 Online:2017-07-05

摘要: 利用EM TP(Electromag netic Transients Pro g ram)电磁暂态计算程序对500 kV 交流同塔四回输电线
路的反击耐雷性能进行了计算和分析。对杆塔高度、冲击接地电阻及避雷线的设置情况等影响反击耐雷性能因素
进行分析, 并且利用该程序分析了雷电流作用下, 塔身和横担的电位以及导线对其相应的上下横担电位差的分布情
况。分析结果表明, 在高杆塔情况下, 降低冲击接地电阻对耐雷性能的改善效果不大;在中横担外侧加设耦合地线
和上横担中部增设避雷线以及适当调整导线与上下横担之间空气间隙的距离可有效的改善输电线路的耐雷性能;
在条件允许的情况下, 建议降低杆塔高度。

关键词: 同塔四回 , 输电线路 , 反击 , 耐雷性能

Abstract:

Lightning performance calculation and analysis of back flashover for 500 kV AC transmission lines with quadruple-circuits on single tower was obtained by electromagnetic transients program (EMTP). Lightning performance influenced by different factors such as grounding resistance, height of tower, and grounding wires was calculated and analyzed in details. Electric potential waveshapes of tower body and crossarms were presented by EMTP, also voltage waveshape between upper or lower crossarms and any given phase conductors. Under the lighting stroke, electric potential of tower body reduces gradually from top to down while that of the top crossarm reduces gradually from one side with lightning stroke to another side without lightning stroke.Voltage everywhere of the middle crossarm is almost same, also of the down one. Voltage between phase conductors and upper crossarm is higher than that between the phase conductors and lower crossarms. As a conclusion, measures to reduce damages brought by back flashover are listed below: reducing height of towers, setting up grounding wires in the center of the top crossarm and both sides of the second crossarm; increasing the air gap distance between phase conductors and their the upper crossarms, etc.

Key words:

引用本文

柴雅静, 周文俊, 李雪,刘小冬,苏红梅. 500 kV 交流同塔四回输电线路反击耐雷性能[J]. 石油化工高等学校学报, 2007, 20(3): 74-77.

CHAI Ya-jing, ZHOU Wen-jun, LI Xue, LIU Xiao-dong, SU Hong-mei. Back Flashovers Lightning Perfo rmances fo r 500 kV AC T ransmission Lines Wi th Quadruple -Circui ts o n Single Tow er[J]. Journal of Petrochemical Universities, 2007, 20(3): 74-77.

使用本文

0
    /   /   推荐

导出引用管理器 EndNote|Ris|BibTeX

链接本文: https://journal.lnpu.edu.cn/syhg/CN/

               https://journal.lnpu.edu.cn/syhg/CN/Y2007/V20/I3/74