石油化工高等学校学报

石油化工高等学校学报 ›› 2011, Vol. 24 ›› Issue (5): 91-94.DOI: 10.3696/j.issn.1006-396X.2011.05.024

• 化工机械 • 上一篇    

单盘外浮顶油罐自动通气阀溢油的原因分析

王立志1,李玉忠2   

  1. (1.天津大学,天津300072;暋2.海工英派尔工程有限公司,山东青岛266061)
  • 收稿日期:2011-07-11 修回日期:2011-09-15 出版日期:2011-10-25 发布日期:2011-10-25
  • 作者简介:王立志(1970-),男,辽宁昌图县,高级工程师,硕士

The Reason Analysis for Oil Spill of The Single-Deck External Floating Roof Oil Tanks Automatic Breather Valve

  1. 1.Tianjin University, Tianjin 300072, P.R.China;2. Marine Pyle Engineering Co. Ltd., Qingdao Shandong 266061, P.R.China
  • Received:2011-07-11 Revised:2011-09-15 Published:2011-10-25 Online:2011-10-25

摘要: 简要介绍了外浮顶油罐自动通气阀的结构形式和工作原理,将外浮顶罐浮盘未升起时浮盘与罐底之间的油气空间类比标准固定,顶罐容积确定热影响容积进行储罐通气量及通气阀通气面积的计算,根据流体稳定流动量方程推导出油品进入自动通气阀阀体内的高度计算公式,确定自动通气阀在通气面积一定时阀杆必须具有的设计高度,进而分析出一些已建油罐可能由于通气阀通气面积不够或阀杆设计高度不足而产生溢油的原因和今后设计应注意的问题。

关键词: 外浮顶油罐,    , 自动通气阀,    , 通气量,    , 阀杆高度,    , 溢油

Abstract: The structural style and working principle of the external floating roof tank's automatic breather valve were briefly introduced.Fixed the analogical standard of the oil vapour space between the factory end and the floating plate when it was unrisen.The volume ofthe roof tank decides the heat affecting volume calculate the tank throughtout and the breathing area of the breather valve.According to the fluid steady flow mathematical equation,deduced the height computing formula of petroleum production flowing into the automatic breather valve.Definite the design height that the valve handle must possess when the breathing area was given.And then analyze the oil spill reasons of the established oil tanks,which may be caused by the lacking of breathing area or the design height of valve handle,and the problems must pay attention to in future design.

Key words: External floating roof tank,    , Automatic ventilation valve,    , Ventilation,    , Stem height,    , Oil spill

引用本文

王立志,李玉忠. 单盘外浮顶油罐自动通气阀溢油的原因分析[J]. 石油化工高等学校学报, 2011, 24(5): 91-94.

WANG Li-zhi,LI Yu-zhong. The Reason Analysis for Oil Spill of The Single-Deck External Floating Roof Oil Tanks Automatic Breather Valve[J]. Journal of Petrochemical Universities, 2011, 24(5): 91-94.

使用本文